The Critical 3 Process
- Primary Amps
Be sure you do not exceed the maximum rated amperage of the transformer (refer to max amp rating on label inside transformer). - Secondary Amps
Be sure you do not exceed the maximum rated amperage of the cable (refer to wire table below). - Voltage at the HUB
Verify HUB voltage is in the optimal voltage range. 12V system (11.5 to 12 volts at the HUB). 24V system (23 to 23.5 volts at the HUB)
Cable Values
Gauge |
Max. Amps |
Resistance |
8 |
40 |
.00064 |
10 |
30 |
.00108 |
12 |
20 |
.00162 |
14 |
15 |
.00252 |
16 |
10 |
.00401 |
18 |
8 |
.00638 |